Circuit Protectors (CBE) CP
Liên hệ: +84-964 654 007 Category: Cầu dao bảo vệ Tag: Circuit Protectors (CBE) CP Maker: Mitsubishi
Description
This kind of breaker complies with UL 1077 and CSA C22.2No.235 and is certified by UL with the classification as recognized component.
Specification
Circuit Protectors
These are mostly used for protection when protection with an MCCB is not possible, such as on low capacity control circuits, heaters, motors, solenoid valves, transformers and electronic circuits. They make it possible to reduce the space required for the equipment and various control circuits such as the control panel. There are detailed differences in the types of rated current available and the lineup includes multiple over current operation characteristics.Features
1. An opening/closing type compact terminal cover is included as standard
- Finger protection is available due to the opening/closing type compact terminal cover and mark tube insulation!(IP20 class from front direction (TÜV certified))
- Additional finger protection from the wiring insertion direction.
- Opening and closing is possible with one touch, so the checking of the terminal part at the panel shipping and witnessed inspections has been made easier.
- The checking of the terminal part during maintenance has been made easier.
- Even with the terminal cover closed, the mark tube symbols are not hidden and can be confirmed with one glance.
- Even with the terminal cover closed, it is possible to perform insulation resistance measurement and continuity inspections.
2. Wide variety of tripping methods
The lineup includes a wide variety of operation characteristics (instantaneous type, high-speed type, medium speed type, low speed type, medium speed type with inertial delay and low speed type with inertial delay), so it is possible to select the type suitable for the protection device.3. Large type terminal cover (Component sold separately)
Large type terminal covers have been prepared as an option for bare solderless terminals.Installation in contact with other devices has been made possible when the terminal cover is attached.
4. AC and DC common type
It is a type for use on both AC and DC, so it can be used as it is for any circuit at or below 250 VAC or 65 VDC. Furthermore, when items are held in inventory, in addition to reducing the storage space, the management work is reduced and there is no mistaken arrangement for AC and DC.5. Reduced space requirements
The width per pole is extremely narrow and compact at just 17.5 mm per pole.This makes a particularly large contribution to the reduction of the space required when the use is in large quantities.Lineup
Model | CP30-BA | CP30-HU | |||||||
---|---|---|---|---|---|---|---|---|---|
Number of poles | 1 | 2 | 3 | 1 | 2 | 3 | |||
Rated current (A) | 0.1 0.25 0.3 0.5 1 2 3 5 7 10 15 20 30 | 0.1 0.25 0.3 0.5 1 2 3 5 | |||||||
Ratedshort-circuitcapacity(kA) | UL 1077CSA C22.2No.235 | Ratedvoltage | AC (V) | 250 | 250 | ||||
DC (V) | 65 | 125 | - | 65 | 125 | - | |||
AC | 2.5kA at 250V | 2.5kA at 250V | 10kA at 250V | ||||||
DC | 2.5kA at 65V | 2.5kA at 125V | - | 10kA at 65V | 10kA at 125V | ||||
IEC 60934EN 60934GB 17701(*3)(Icn) | Ui (V) | 250 | 250 | ||||||
AC | 2.5kA at 230V | 2.5kA at 230V10kA at 120V | 10kA at 230V | ||||||
DC | 2.5kA at 60V | 2.5kA at 120V | - | 10kA at 65V | 10kA at 120V | ||||
IEC 60947-2EN 60947-2JIS C 8201-2-1Ann.1 (Icu/Ics) | Ui (V) | 250 | 250 | ||||||
AC | 2.5/2.5kA at 230V | 2.5/2.5kA at 230V10/10kA at 120V | 10/10kA at 230V | ||||||
DC | 2.5/2.5kA at 120V | - | 10/10kA at 60V | 10/10kA at 120V | |||||
AC/DC common use | common | -(*1) | common | -(*1) | |||||
Mode of tripping | Instantaneous type(I);Medium type(M), (MD);Slow type(S), (SD);Fast type(F)(*2) | Instantaneous type(I);Medium type(M), (MD);Slow type(S) | |||||||
Body mounting method | IEC 35mm rail mounting | IEC 35mm rail mounting |
*(1) The 3-pole products are for AC use only.(2) Contact us for operating characteristics other than those mentioned above.(3) CP30-BA only.
Internal accessories
Auxiliary switch (AX)
Operates combined with the main circuit operating mechanism to electrically retrieve the ON/OFF status of protector.Alarm switch (AL)
Operates combined with the main circuit operating mechanism to electrically retrieve the tripping status of protector.Remarks:
- (1) When the handle of CP30-BA is constrained in the ON status, it does not issue the alarm signal even if it is tripped.
- (2) The alarm switch will be reset when the body is reset or turned on.
Shunt trip (SHT)
SHT can break the circuit instantaneously when the operating voltage is applied on SHT coil.Table 1 List of numbers of internal accessories which can be fitted
Ratings of alarm switches (AL) and auxiliary switches (AX) for CP30-BA
Classification | AC | DC | ||||||
---|---|---|---|---|---|---|---|---|
Voltage(V) | Current (A) | Voltage(V) | Current (A) | |||||
Resistive load | Inductive load | Resistive load | Inductive load | |||||
Ratings ofitems otherthan thoseshaded inTable 1 | For generalload | Max. | (250) | (1) | (0.5) | 50 | 1 | 0.5 |
(250) | (1) | (0.5) | 50 | 1 | 0.5 | |||
Min. | 0.1A/15VAC | 0.1A/15VDC | ||||||
For minuteload | Max. | 125 | 0.5 | - | 30 | 0.5 | - | |
Min. | 1mA/24VDC, 2mA/12VDC, 5mA/6VDC | |||||||
Ratings ofitems shadedin Table 1 | For generalload | Max. | (250) | (1) | (0.5) | (50) | (1) | (0.5) |
125 | 3 | (1) | 30 | (2), 0.5 | (1) | |||
Min. | 0.1A/15VAC | 0.1A/15VDC | ||||||
For minuteload | Max. | 125 | (0.5), 0.1 | - | 30 | (0.5), 0.1 | - | |
Min. | 1mA/24VDC, 2mA/12VDC, 5mA/6VDC |
Remark:
- 1. The switches having the ratings in parentheses are manufactured at the customer's request. (Specify the voltage). Such switches do not conform to UL (cURus), CCC or CE Marking requirements.
Ratings of shunt trip (SHT) coils for CP30-BA
Ratings
Rated operating voltage (V) | Time rating | |
---|---|---|
100-200 | Compatible with 100 to 200 V AC and 100 V DC | 10 sec or less |
24-48 | Compatible with 24 to 48 V DC |
Coil resistance, resistance and impedance(at25°C)
Voltage (V) | Impedance for AC (Ω) | DC resistance for DC (Ω) |
---|---|---|
24-48 | - | 160 |
100-200 | 2400 | 2100 |
Remarks:
- 1. The allowable range is 70 to 110% of the rated voltage for AC and 75 to 120% of the rated voltage for DC.
- 2. The time rating is 10 seconds or less. Configure the circuit on which voltage will not be applied for more than 10 seconds.