Power ratings | 15 W | 30 W | ||||||
---|---|---|---|---|---|---|---|---|
Output voltage | 5 V | 12 V | 24 V | 5 V | 12 V | 24 V | ||
Efficiency | With 100-VAC input | 74% typical | 79% typical | 83% typical | 74% typical | 81% typical | 85% typical | |
With 200-VAC input | 73% typical | 78% typical | 80% typical | 74% typical | 80% typical | 86% typical | ||
Input | Voltage *1 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *5) | ||||||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | |||||||
Current | With 100-VAC input | 0.45 A max., 0.34 A typical | 0.9 A max., 0.66 A typical | |||||
With 200-VAC input | 0.25 A max., 0.22 A typical | 0.6 A max., 0.4 A typical | ||||||
Power factor | --- | |||||||
Harmonic current regulation | Conforms to EN61000-3-2 | |||||||
Leakagecurrent | With 100-VAC input | 0.5 mA max. | ||||||
With 200-VAC input | 1.0 mA max. | |||||||
Inrushcurrent*2 | With 100-VAC input | 17.5 A max., 14 A typical | ||||||
With 200-VAC input | 35 A max., 28 A typical | |||||||
Output | Voltage adjustment range *3 | - 10% to 15% (with V.ADJ) | ||||||
Ripple noise voltage (at rated I/O) | 60 mV max. | 70 mV max. | 60 mV max. | 60 mV max. | 90 mV max. | 150 mV max. | ||
Input variation influence | 0.5% max. (at 85- to 264-VAC input, 100% load) | |||||||
Load variation influence(rated input voltage) | 2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load) | |||||||
Temperature variation influence | 0.05%/°C max. | |||||||
Startup time(at rated I/O) *2 | With 100-VAC input | 580 ms typical | 530 ms typical | 600 ms typical | 500 ms typical | 560 ms typical | 560 ms typical | |
With 200-VAC input | 340 ms typical | 360 ms typical | 400 ms typical | 360 ms typical | 380 ms typical | 400 ms typical | ||
Output hold time(at rated I/O) *2 | With 100-VAC input | 39 ms typical | 27 ms typical | 28 ms typical | 31 ms typical | 22 ms typical | 31 ms typical | |
With 200-VAC input | 187 ms typical | 134 ms typical | 134 ms typical | 174 ms typical | 123 ms typical | 140 ms typical | ||
Additionalfunctions | Overload protection *2 | The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). | ||||||
Overvoltage protection *2 | Yes *4 | |||||||
Output voltage indication | No | |||||||
Output current indication | No | |||||||
Peak-hold current indication | No | |||||||
Maintenance forecast monitor indication | No | |||||||
Maintenance forecast monitor output | No | |||||||
Total run time monitor indication | No | |||||||
Total run time monitor output | No | |||||||
Undervoltage alarm indication | Yes (color: red) | |||||||
Undervoltage alarm output | No | |||||||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | |||||||
Series operation | Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)Models with 5- or 12-V output: Not possible | |||||||
Other | Operating ambient temperature | Refer to the derating curve in Engineering Data. (with no icing or condensation) | ||||||
Storage temperature | - 25 to 65°C | |||||||
Operating ambient humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) | |||||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC | |||||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions | |||||||
Shock resistance | 150 m/s2 , 3 times each in ±X, ±Y, and ±Z directions | |||||||
Output indicator | Yes (color: green) | |||||||
EMI | Conducted Emissions | Conforms to EN55011 Group1 Class B and based on FCC Class A | ||||||
Radiated Emissions | Conforms to EN55011 Group1 Class B | |||||||
EMS | Conforms to EN61204-3 high severity levels | |||||||
Approved standards | UL 508 (Listing, Class2 Output: Per 1310)UL 60950-1, UL 62368-1CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)CSA C22.2 No.60950-1 (cUR), No.62368-1EN 50178, EN 60950-1, EN 62368-1EAC mark, RCM mark | |||||||
SEMI | F47-0706 (With 200-VAC input) | |||||||
Weight | 160 g max. | 180 g max. |
Omron S8VS Power Supply
Công ty Tự Động Hóa VIETFA chuyên cung cấp bộ nguồn S8VS của Omron
Liên hệ: +84-964 654 007 Category: Indication monitor type Tags: Bộ nguồn Omron, Omron VietNam Maker: Omron
Description
• Status displayed on 3-digit, 7-segment display. *
• Signal output notifications at 90 W or more. *
• Conformity to various safety standards for global usability.
• Varied coverage with 3-year warranty.
* Models with indication monitor
Specification
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, butthe rise in the internal temperature of the Power Supply may result in ignition or burning.*2. For a cold start at 25°C. Refer to Engineering Data on Data Sheet for details.*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltageadjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and besure that the load is not damaged.*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.*5. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings | 60 W | ||||
---|---|---|---|---|---|
Type | Standard | Maintenance forecastmonitor | Total run timemonitor | ||
Efficiency | With 100-VAC input | 84% typical | 83% typical | ||
With 200-VAC input | 83% typical | 85% typical | |||
Input | Voltage *1 | 100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11) | |||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | ||||
Current | With 100-VAC input | 1.7 A max., 1.3 A typical | 1.7 A max., 1.3 A typical | ||
With 200-VAC input | 1.0 A max., 0.68 A typical | 1.0 A max., 0.78 A typical | |||
Power factor | --- | ||||
Harmonic current regulation | Conforms to EN61000-3-2 | ||||
Leakage current | With 100-VAC input | 0.5 mA max. | |||
With 200-VAC input | 1.0 mA max. | ||||
Inrush current *2 | With 100-VAC input | 17.5 A max., 14 A typical | |||
With 200-VAC input | 35 A max., 28 A typical | ||||
Output | Voltage adjustment range *3 | -10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024[][][]S-[].) | |||
Ripple noise voltage (at rated I/O) | 70 mV max. | 90 mV max. | |||
Input variation influence | 0.5% max. (at 85- to 264-VAC input, 100% load) | ||||
Load variation influence (rated input voltage) | 1.5% max. (with rated input, 0 to 100% load) | ||||
Temperature variation influence | 0.05%/°C max. | ||||
Startup time(at rated I/O) *2 | With 100-VAC input | 620 ms typical | 460 ms typical | ||
With 200-VAC input | 400 ms typical | 290 ms typical | |||
Output hold time(at rated I/O) *2 | With 100-VAC input | 34 ms typical | 33 ms typical | ||
With 200-VAC input | 158 ms typical | 154 ms typical | |||
Additionalfunctions | Overload protection *2 | 105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024[][][]S-[]),inverted L voltage drop, intermittent, automatic reset | |||
Overvoltage protection *2, *4 | Yes | ||||
Output voltage indication *5 | No | Yes (selectable) *6 | |||
Output current indication *5 | No | Yes (selectable) *7 | |||
Peak-hold current indication *5 | No | Yes (selectable) *8 | |||
Maintenance forecast monitor indication *5 | No | Yes (selectable) | No | ||
Maintenance forecast monitor output | No | ||||
Total run time monitor indication *5 | No | Yes (selectable) | |||
Total run time monitor output *5 | No | ||||
Undervoltage alarm indication *5 | No | Yes (selectable) | |||
Undervoltage alarm output terminals | No | ||||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | ||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | ||||
Other | Operating ambient temperature | Refer to the derating curve in . (with no icing or condensation) | |||
Storage temperature | -25 to 65°C | ||||
Operating ambient humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detectioncurrent for models with indication monitor: 20 mA)500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA) | ||||
Insulation resistance | 100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC | ||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions | ||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | ||||
Output indicator | Yes (color: green) | ||||
EMI | ConductedEmissions | Models with indication monitor: Conforms to EN55011 Group1 Class A and based on FCC Class A,Conforms to EN55011 Group1 Class B *11Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A | |||
RadiatedEmissions | Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms to EN55011 Group1 Class B *11Standard models: Conforms to EN55011 Group1 Class B | ||||
EMS | Conforms to EN61204-3 high severity levels | ||||
Approved standards *11 | Standard model:UL 508 (Listing; Class 2 Output: Per UL1310)UL 60950-1 (Recognition), UL 62368-1CSA C22.2 No.107.1 (cUL) (Class 2 Output: Per CSA C22.2 No. 223)CSA C22.2 No.60950-1 (cUR), No.62368-1EN 50178, EN 60950-1, EN 62368-1EAC mark, RCM markWith indication monitor:UL 508 (Listing, Class2 Output: Per 1310)CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)EN 62477-1EAC mark, RCM mark, KOSHA S Mark *10 | ||||
SEMI *11 | F47-0706 (With 200-VAC input) | ||||
Weight | 330 g max. |
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.*2. For a cold start at 25°C. Refer to Engineering Data on data sheet for details.*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.*5. Displayed on 7-segment LED. (character height: 8 mm)*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);Signal width required for peak-hold current: 20 ms*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings | 90 W | ||||
---|---|---|---|---|---|
Type | Standard | Maintenance forecastmonitor | Total run timemonitor | ||
Efficiency | With 100-VAC input | 83% typical | 83% typical | ||
With 200-VAC input | 84% typical | 85% typical | |||
Input | Voltage *1 | 100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11) | |||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | ||||
Current | With 100-VAC input | 2.3 A max., 1.9 A typical | 2.3 A max., 1.9 A typical | ||
With 200-VAC input | 1.4 A max., 1.0 A typical | 1.4 A max., 1.2 A typical | |||
Power factor | --- | ||||
Harmonic current regulation | Conforms to EN61000-3-2 | ||||
Leakage current | With 100-VAC input | 0.5 mA max. | |||
With 200-VAC input | 1.0 mA max. | ||||
Inrush current *2 | With 100-VAC input | 17.5 A max., 14 A typical | |||
With 200-VAC input | 35 A max., 28 A typical | ||||
Output | Voltage adjustment range *3 | -10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024[][][]S-[].) | |||
Ripple noise voltage (at rated I/O) | 250 mV max. | 150 mV max. | |||
Input variation influence | 0.5% max. (at 85- to 264-VAC input, 100% load) | ||||
Load variation influence (rated input voltage) | 1.5% max. (with rated input, 0 to 100% load) | ||||
Temperature variation influence | 0.05%/°C max. | ||||
Startup time(at rated I/O) *2 | With 100-VAC input | 460 ms typical | 660 ms typical | ||
With 200-VAC input | 300 ms typical | 420 ms typical | |||
Output hold time(at rated I/O) *2 | With 100-VAC input | 28 ms typical | 28 ms typical | ||
With 200-VAC input | 132 ms typical | 136 ms typical | |||
Additionalfunctions | Overload protection *2 | 105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024[][][]S-[]),inverted L voltage drop, intermittent, automatic reset | |||
Overvoltage protection *2, *4 | Yes | ||||
Output voltage indication *5 | No | Yes (selectable) *6 | |||
Output current indication *5 | No | Yes (selectable) *7 | |||
Peak-hold current indication *5 | No | Yes (selectable) *8 | |||
Maintenance forecast monitor indication *5 | No | Yes (selectable) | No | ||
Maintenance forecast monitor output | No | Yes (transistor output), 30 VDC max., 50 mA max. *9 | No | ||
Total run time monitor indication *5 | No | Yes (selectable) | |||
Total run time monitor output *5 | No | Yes (transistor output),30 VDC max., 50 mA max. *9 | |||
Undervoltage alarm indication *5 | No | Yes (selectable) | |||
Undervoltage alarm output terminals | No | Yes (transistor output), 30 VDC max., 50 mA max. *9 | |||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | ||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | ||||
Other | Operating ambient temperature | Refer to the derating curve in . (with no icing or condensation) | |||
Storage temperature | -25 to 65°C | ||||
Operating ambient humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current forstandard models: 30 mA, detection current for models with indication monitor: 20 mA)500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA) | ||||
Insulation resistance | 100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC | ||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions | ||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | ||||
Output indicator | Yes (color: green) | ||||
EMI | ConductedEmissions | Models with indication monitor: Conforms to EN55011 Group1 Class A and based on FCC Class A,Conforms to EN55011 Group1 Class B *11Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A | |||
RadiatedEmissions | Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms to EN55011 Group1Class B *11Standard models: Conforms to EN55011 Group1 Class B | ||||
EMS | Conforms to EN61204-3 high severity levels | ||||
Approved standards *11 | Standard model:UL 508 (Listing)(S8VS-09024S-[] only): UL 508 (Listing, Class2 Output: Per 1310)UL 60950-1 (Recognition), UL 62368-1CSA C22.2 No.107.1 (cUL)(S8VS-09024S-[] only): CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)CSA C22.2 No.60950-1 (cUR), No.62368-1EN 50178, EN 60950-1, EN 62368-1EAC mark, RCM markWith indication monitor:UL 508 (Listing)(S8VS-09024[][]S-[] only): UL 508 (Listing, Class2 Output: Per 1310)CSA C22.2 No.107.1(S8VS-09024[][]S-[] only): CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)EN 62477-1EAC mark, RCM mark, KOSHA S Mark *10 | ||||
SEMI *11 | F47-0706 (With 200-VAC input) | ||||
Weight | 490 g max. |
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.*2. For a cold start at 25°C. Refer to Engineering Data on data sheet for details.*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.*5. Displayed on 7-segment LED. (character height: 8 mm)*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);Signal width required for peak-hold current: 20 ms*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings | 120 W | 180 W | ||||||
---|---|---|---|---|---|---|---|---|
Type | Standard | Maintenanceforecast monitor | Total run timemonitor | Standard | Maintenanceforecast monitor | Total run timemonitor | ||
Efficiency | With 100-VAC input | 84% typical | 83% typical | 85% typical | 85% typical | |||
With 200-VAC input | 87% typical | 85% typical | 88% typical | 87% typical | ||||
Input | Voltage *1 | 100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11) | ||||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||||
Current | With 100-VAC input | 1.9 A max., 1.5 A typical | 2.9 A max., 2.2 A typical | |||||
With 200-VAC input | 1.1 A max.,0.71 A typical | 1.1 A max., 0.72 A typical | 1.6 A max., 1.1 A typical | |||||
Power factor | 0.9 min. | |||||||
Harmonic current regulation | Conforms to EN61000-3-2 | |||||||
Leakage current | With 100-VAC input | 0.5 mA max. | ||||||
With 200-VAC input | 1.0 mA max. | |||||||
Inrush current*2 | With 100-VAC input | 17.5 A max., 14 A typical | ||||||
With 200-VAC input | 35 A max., 28 A typical | |||||||
Output | Voltage adjustment range *3 | - 10% to 15% (with V.ADJ) | ||||||
Ripple noise voltage (at rated I/O) | 60 mV max. | 130 mV max. | 50 mV max. | 180 mV max. | ||||
Input variation influence | 0.5% max. (at 85- to 264-VAC input, 100% load) | |||||||
Load variation influence (rated input voltage) | 1.5% max. (with rated input, 0 to 100% load) | |||||||
Temperature variation influence | 0.05%/°C max. | |||||||
Startup time(at rated I/O) *2 | With 100-VAC input | 550 ms typical | 650 ms typical | 570 ms typical | 580 ms typical | |||
With 200-VAC input | 400 ms typical | 520 ms typical | 470 ms typical | 490 ms typical | ||||
Output hold time(at rated I/O) *2 | With 100-VAC input | 52 ms typical | 56 ms typical | 58 ms typical | 70 ms typical | |||
With 200-VAC input | 54 ms typical | 56 ms typical | 62 ms typical | 70 ms typical | ||||
Additionalfunctions | Overload protection *2 | 105% to 160% of rated load current, inverted L voltage drop, automatic reset | ||||||
Overvoltage protection *2, *4 | Yes | |||||||
Output voltage indication *5 | No | Yes (selectable) *6 | No | Yes (selectable) *6 | ||||
Output current indication *5 | No | Yes (selectable) *7 | No | Yes (selectable) *7 | ||||
Peak-hold current indication *5 | No | Yes (selectable) *8 | No | Yes (selectable) *8 | ||||
Maintenance forecast monitor indication *5 | No | Yes (selectable) | No | No | Yes (selectable) | No | ||
Maintenance forecast monitor output | No | Yes (transistoroutput), 30 VDCmax., 50 mA max.*9 | No | No | Yes (transistoroutput), 30 VDCmax., 50 mA max.*9 | No | ||
Total run time monitor indication *5 | No | Yes (selectable) | No | Yes (selectable) | ||||
Total run time monitor output *5 | No | Yes(transistoroutput), 30VDC max., 50mA max. *9 | No | Yes (transistoroutput), 30 VDCmax., 50 mA max.*9 | ||||
Undervoltage alarm indication *5 | No | Yes (selectable) | No | Yes (selectable) | ||||
Undervoltage alarm output terminals | No | Yes (transistor output),30 VDC max., 50 mA max. *9 | No | Yes (transistor output),30 VDC max., 50 mA max. *9 | ||||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | |||||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | |||||||
Other | Operating ambient temperature | Refer to the derating curve in Engineering Data. (with no icing or condensation) | ||||||
Storage temperature | - 25 to 65°C | |||||||
Operating ambient humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs/alarm outputs; detectioncurrent: 20 mA)2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)1.0 kVAC for 1 min. (between all outputs/alarm outputs and PE terminals; detectioncurrent for standard models: 30 mA, detection current for models with indicationmonitor: 20 mA500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20mA) | |||||||
Insulation resistance | 100 MΩ min. (between all outputs/alarm outputs and all inputs/PE terminals) at500 VDC | |||||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Zdirections | |||||||
Shock resistance | 150 m/s2 , 3 times each in ±X, ±Y, and ±Z directions | |||||||
Output indicator | Yes (color: green) | |||||||
EMI | Conducted Emissions | Models with indication monitor: Conforms to EN55011 Group1 Class A and basedon FCC Class A, Conforms to EN55011 Group1 Class B *11Standard models: Conforms to EN55011 Group1 Class B and based on FCCClass A | ||||||
Radiated Emissions | Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms toEN55011 Group1 Class B *11Standard models: Conforms to EN55011 Group1 Class B | |||||||
EMS | Conforms to EN61204-3 high severity levels | |||||||
Approved standards *11 | UL 508 (Listing)CSA C22.2 No. 107.1 (cUL)EN 62477-1EAC mark, RCM mark, KOSHA S Mark *10 | |||||||
SEMI *11 | F47-0706 (200-VAC input) | |||||||
Weight | 550 g max. | 850 g max. |
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.*2. For a cold start at 25°C. Refer to Engineering Data on data sheet for details.*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.*5. Displayed on 7-segment LED. (character height: 8 mm)*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);Signal width required for peak-hold current: 20 ms*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings | 240 W | 480 W | ||||||
---|---|---|---|---|---|---|---|---|
Item Type | Standard | Maintenanceforecast monitor | Total run timemonitor | Standard | Maintenanceforecast monitor | Total run timemonitor | ||
Efficiency | With 100-VAC input | 85% typical | 89% typical | |||||
With 200-VAC input | 88% typical | 93% typical | ||||||
Input | Voltage *1 | 100 to 240 VAC (allowable range: 85 to264 VAC or 80 to 370 VDC *11) | 100 to 240 VAC (allowable range: 85 to264 VAC) | |||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||||
Current | With 100-VAC input | 3.8 A max., 2.9 A typical | 7.4 A max., 5.8 A typical | |||||
With 200-VAC input | 2.0 A max., 1.5 A typical | 3.9 A max., 2.8 A typical | ||||||
Power factor | 0.9 min. | 0.95 min. | ||||||
Harmonic current regulation | Conforms to EN61000-3-2 | |||||||
Leakage current | With 100-VAC input | 0.5 mA max. | ||||||
With 200-VAC input | 1.0 mA max. | |||||||
Inrush current*2 | With 100-VAC input | 17.5 A max., 14 A typical | ||||||
With 200-VAC input | 35 A max., 28 A typical | |||||||
Output | Voltage adjustment range *3 | - 10% to 15% (with V.ADJ) | -10% to 15% (with V.ADJ) | |||||
Ripple noise voltage (at rated I/O) | 140 mV max. | 160 mV max. | 310 mV max. | |||||
Input variation influence | 0.5% max. (at 85- to 264-VAC input, 100% load) | |||||||
Load variation influence(rated input voltage) | 1.5% max. (with rated input, 0 to 100% load) | |||||||
Temperature variation influence | 0.05%/°C max. | |||||||
Startup time(at rated I/O) *2 | With 100-VAC input | 540 ms typical | 510 ms typical | 550 ms typical | ||||
With 200-VAC input | 230 ms typical | 510 ms typical | 550 ms typical | |||||
Output hold time(at rated I/O) *2 | With 100-VAC input | 64 ms typical | 46 ms typical | 37 ms typical | ||||
With 200-VAC input | 64 ms typical | 46 ms typical | 41 ms typical | |||||
Additionalfunctions | Overload protection *2 | 105% to 160% of rated load current, invertedL voltage drop, automatic reset | 151% to 165% of rated load current, invertedL voltage drop, intermittent, automatic reset | |||||
Overvoltage protection *2, *4 | Yes | |||||||
Output voltage indication *5 | No | Yes (selectable) *6 | No | Yes (selectable) *6 | ||||
Output current indication *5 | No | Yes (selectable) *7 | No | Yes (selectable) *7 | ||||
Peak-hold current indication *5 | No | Yes (selectable) *8 | No | Yes (selectable) *8 | ||||
Maintenance forecast monitor indication *5 | No | Yes (selectable) | No | Yes (selectable) | No | |||
Maintenance forecast monitor output | No | Yes(transistor output),30 VDC max., 50 mAmax. *9 | No | Yes(transistor output),30 VDC max., 50 mAmax. | No | |||
Total run time monitor indication *5 | No | Yes (selectable) | No | Yes(selectable) | ||||
Total run time monitor output *5 | No | Yes(transistor output),30 VDC max., 50 mAmax. *9 | No | Yes(transistor output),30 VDC max., 50 mAmax. *9 | ||||
Undervoltage alarm indication *5 | No | Yes (selectable) | No | Yes (selectable) | ||||
Undervoltage alarm output terminals | No | Yes (transistor output),30 VDC max., 50 mA max. *9 | No | Yes (transistor output),30 VDC max., 50 mA max. *9 | ||||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | |||||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | |||||||
Other | Operating ambienttemperature | Refer to the derating curve in Engineering Data. (with no icing or condensation) | ||||||
Storage temperature | - 25 to 65°C | |||||||
Operating ambienthumidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs/alarm outputs; detectioncurrent: 20 mA)2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)1.0 kVAC for 1 min. (between all outputs/alarm outputs and PE terminals; detectioncurrent for standard 240-W and 480-W models: 30 mA, detection current for 240-Wmodels with indication monitor: 20 mA)500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA) | |||||||
Insulation resistance | 100 MΩ min. (between all outputs/alarm outputs and all inputs/PE terminals) at 500VDC | |||||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Zdirections: 240 W10 to 150 Hz, 0.35-mm single amplitude (3 G max.) for 80 min each in X, Y, and Zdirections: 480 W | |||||||
Shock resistance | 150 m/s2 , 3 times each in ±X, ±Y, and ±Z directions | |||||||
Output indicator | Yes (color: green) | |||||||
EMI | ConductedEmissions | Models with indication monitor: Conforms to EN55011 Group1Class A and based on FCC Class A, Conforms to EN55011Group1 Class B *11Standard models: Conforms to EN55011 Group1 Class B andbased on FCC Class A | Conforms to EN55011 Group1 Class A and based on FCCClass AConforms to EN55011 Group1 Class B *11 | |||||
Radiated Emissions | Models with indication monitor: Conforms to EN55011 Group1Class A, Conforms to EN55011 Group1 Class B *11Standard models: Conforms to EN55011 Group1 Class B | Conforms to EN55011 Group1 Class AConforms to EN55011 Group1 Class B *11 | ||||||
EMS | Conforms to EN61204-3 high severity levels | |||||||
Approved standards *11 | UL 508 (Listing)CSA C22.2 No.107.1 (cUL)EN 62477-1EAC mark, RCM mark, KOSHA S Mark *10 | UL 508 (Listing)UL 60950-1 (Recognition)UL 62368-1 (Recognition)CSA C22.2 No.107.1 (cUL)CSA C22.2 No. 60950-1 (cUR), No. 62368-1 (cUR)EN 50178 (=VDE 0160), EN 60950-1 (=VDE 0805 Teil 1)EAC mark, RCM mark | ||||||
SEMI *11 | F47-0706 (200-VAC input) | |||||||
Weight | 1,150 g max. | 1,700 g max. |
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.*2. For a cold start at 25°C. Refer to Engineering Data on data sheet for details.*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.*5. Displayed on 7-segment LED. (character height: 8 mm)*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);Signal width required for peak-hold current: 20 ms*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Model List
Powerratings | Input voltage | Outputvoltage | Output current | UL Class 2Outputstandards | Model number(screw terminalblock) | Model number(screwlessterminal block) |
---|---|---|---|---|---|---|
15 W | 100 to 240 VAC(allowable range:85 to 264 VAC or80 to 370 VDC *3) | 5 V | 2.0 A | Yes | S8VS-01505 *1 | --- |
12 V | 1.2 A | Yes | S8VS-01512 | |||
24 V | 0.65 A | Yes | S8VS-01524 | |||
30 W | 5 V | 4.0 A | Yes | S8VS-03005 *2 | ||
12 V | 2.5 A | Yes | S8VS-03012 | |||
24 V | 1.3 A | Yes | S8VS-03024 | |||
60 W | 24 V | 2.5 A | Yes | S8VS-06024 | S8VS-06024-F | |
90 W | 3.75 A | --- | S8VS-09024 | S8VS-09024-F | ||
Yes | S8VS-09024S | S8VS-09024S-F | ||||
120 W | 5 A | --- | S8VS-12024 | S8VS-12024-F | ||
180 W | 7.5 A | --- | S8VS-18024 | S8VS-18024-F | ||
240 W | 10 A | --- | S8VS-24024 | S8VS-24024-F | ||
480 W | 100 to 240 VAC | 20 APeak current 30 A(200 VAC) | --- | S8VS-48024 | S8VS-48024-F |
*1. The output capacity of the S8VS-01505 is 10 W.*2. The output capacity of the S8VS-03005 is 20 W.*3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Models with Indication Monitor (Maintenance Forecast Monitor)
Powerratings | Inputvoltage | Outputvoltage | Outputcurrent | Alarmoutput*2 | UL Class 2Outputstandards | Model number(screw terminallock) | Model number(screwlessterminal block) |
---|---|---|---|---|---|---|---|
60 W | 100 to 240VAC(allowablerange: 85 to264 VAC or80 to 370VDC *1) | 24 V | 2.5 A | --- | Yes | S8VS-06024A | S8VS-06024A-F |
90 W | 3.75 A | Sinking | --- | S8VS-09024A | S8VS-09024A-F | ||
Sinking | Yes | S8VS-09024AS | S8VS-09024AS-F | ||||
Sourcing | --- | S8VS-09024AP | S8VS-09024AP-F | ||||
Sourcing | Yes | S8VS-09024APS | S8VS-09024APS-F | ||||
120 W | 5 A | Sinking | --- | S8VS-12024A | S8VS-12024A-F | ||
Sourcing | --- | S8VS-12024AP | S8VS-12024AP-F | ||||
180 W | 7.5 A | Sinking | --- | S8VS-18024A | S8VS-18024A-F | ||
Sourcing | --- | S8VS-18024AP | S8VS-18024AP-F | ||||
240 W | 10 A | Sinking | --- | S8VS-24024A | S8VS-24024A-F | ||
Sourcing | --- | S8VS-24024AP | S8VS-24024AP-F | ||||
480 W | 100 to 240VAC | 20 APeak current30 A (200 VAC) | Sinking/sourcing | --- | S8VS-48024A | S8VS-48024A-F |
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).*2. In the Alarm output column,"sinking" indicates an emitter COM and "sourcing" indicates a collector COM.
Models with Indication Monitor (Total Run Time Monitor)
Powerratings | Inputvoltage | Outputvoltage | Outputcurrent | Alarmoutput*2 | UL Class 2Outputstandards | Model number(screw terminalblock) | Model number(screwlessterminal block) |
---|---|---|---|---|---|---|---|
60 W | 100 to 240VAC(allowablerange: 85 to264 VAC or80 to 370VDC) *1 | 24 V | 2.5 A | --- | Yes | S8VS-06024B | S8VS-06024B-F |
90 W | 3.75 A | --- | --- | S8VS-09024BE | S8VS-09024BE-F | ||
--- | Yes | S8VS-09024BES | S8VS-09024BES-F | ||||
Sinking | --- | S8VS-09024B | S8VS-09024B-F | ||||
Sinking | Yes | S8VS-09024BS | S8VS-09024BS-F | ||||
Sourcing | --- | S8VS-09024BP | S8VS-09024BP-F | ||||
Sourcing | Yes | S8VS-09024BPS | S8VS-09024BPS-F | ||||
120 W | 5 A | --- | --- | S8VS-12024BE | S8VS-12024BE-F | ||
Sinking | --- | S8VS-12024B | S8VS-12024B-F | ||||
Sourcing | --- | S8VS-12024BP | S8VS-12024BP-F | ||||
180 W | 7.5 A | --- | --- | S8VS-18024BE | S8VS-18024BE-F | ||
Sinking | --- | S8VS-18024B | S8VS-18024B-F | ||||
Sourcing | --- | S8VS-18024BP | S8VS-18024BP-F | ||||
240 W | 10 A | --- | --- | S8VS-24024BE | S8VS-24024BE-F | ||
Sinking | --- | S8VS-24024B | S8VS-24024B-F | ||||
Sourcing | --- | S8VS-24024BP | S8VS-24024BP-F | ||||
480 W | 100 to 240VAC | 20 APeak current30 A (200 VAC) | Sinking/sourcing | --- | S8VS-48024B | S8VS-48024B-F |
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).*2. In the Alarm output column, "sinking" indicates an emitter COM and "sourcing" indicates a collector COM.Note: Refer to Data Sheet for the options that available.
Terminal Block Cover (Order Separately)
S8VS | Input side | Output side |
---|---|---|
15W | S82Y-VS-C2P-S | |
30W | S82Y-VS-C2P-S | |
60W | S82Y-VS-C3P | S82Y-VS-C2P-M |
90W | S82Y-VS-C3P | S82Y-VS-C2P-M |
120W | S82Y-VS-C3P | S82Y-VS-C2P-M |
180W | S82Y-VS-C3P | S82Y-VS-C4P |
240W | S82Y-VS-C3P | S82Y-VS-C4P |
480W | S82Y-VS-C3P |
Note: Terminal block cover attaches to the body. Please order from the loss time.
Mounting Brackets
Name | Model |
---|---|
Side-mounting Bracket (for 15- and 30-W models) | S82Y-VS30P |
Side-mounting Bracket (for 60-, 90-, and 120-W models) | S82Y-VS10S |
Side-mounting Bracket (for 180-W models) | S82Y-VS15S |
Side-mounting Bracket (for 240-W models) | S82Y-VS20S |
Front-mounting Bracket (for 60-, 90-, 120-, 180-, and 240-W models) * | S82Y-VS10F |
Note: Brackets cannot be used for 480-W models.* Two required to mount a 240-W model.